3.1 FR/FR-LS Multistrand single core wires

Description

Size: 0.75 sq.mm to 300 sq.mm
Colour:Availability

0.75 sq.mm : Green

1.0 sq,mm to 4 sq,mm:Red, Yellow,
Yellow / Black,Blue,Green,White & Grey

Cond.Area Max conductor resistance at 20*C Nom Thickness of Insulation Appx.Dia over Insulation Nom.Sheath Thikness
Enclosed in Conduit/Trunking Unenclosed clipped to a surface or on cable tray
Sq.mm mm. mm. Ohms/km Amps Amps.
1.0 0.70 2.8 18.10 11 12
1.5 0.70 3.1 12.10 13 16
2.5 0.80 3.8 7.14 18 22
4.0 0.80 4.6 4.95 24 19
6.0 0.80 5.3 3.30 31 37

FR/FR-LS Multistrand single core wires

Description

6 sq.mm to 70 sq.mm
Red ,Yellow, Black, Blue & Green

Cond.Area Max conductor resistance at 20*C Nom Thickness of Insulation Appx.Dia over Insulation Current carrying capacity bunched & enclosed in Conduit or Trunking Current carrying capacity clipped direct to a surface or on Cable tray bunched & Unenclosed
2 cables single phase ac or dc 3 or 4 cables 3 phase ac 2 cables single phase ac or dc 3 or 4 cables 3 phase ac
Sq.mm Ohms/km mm. mm. Amps Amps. Amps. Amps.
10 1.0 6.5 1.91 42 35 51 45
16 1.0 7.5 1.21 57 48 68 61
25 1.2 9.5 0.780 71 60 86 75
35 1.2 10.5 0.554 91 77 110 99
50 1.4 12.0 0.386 120 100 145 135

FR/FR-LS Multistrand single core wires

Description

95 sq.mm to 300 sq.mm: Black

Nominal Area of conductor Nominal Thickness of Insulation Appx.Overall Diameter Max conductor resistance at 20*C Current carrying capacity clipped direct to a surface or on Cable tray bunched & Unenclosed Current carrying capacity
2 cables single phase ac or dc 3 or 4 cables 3 phase ac Flat or Vertical 2 cables single phase ac or dc or 3 or 4 cables 3 phase ac 3 or 4 cables 3 phase ac
Sq.mm mm. mm. Ohms/km Amps Amps. Amps. Amps.
70 1.4 14.5 0.272 200 180 215 185
95 1.6 16.0 0.206 235 215 260 230
120 1.6 18.5 0.161 270 240 305 267
150 1.8 21.0 0.129 310 280 355 305
185 2.0 23.0 0.106 360 320 415 350
240 2.2 27.0 0.080 425 385 500 420
300 2.4 30.0 0.064 490 440 585 490

Send Enquiry